1 “HARMONICS” Causes, Effects, Solutions K - FACTOR TRANSFORMERS HARMONIC MITIGATING TRANSFORMERS I-TRAP NEUTRAL CURRENT REDUCER

2 WHAT ARE HARMONICS ? HARMONICS: A sinusoidal waveform with a frequency that is an integral multiple of the fundamental frequency. 60hz Fundamental 120hz 2nd Harmonic 180hz 3rd Harmonic 240hz 4th Harmonic etc... Note: Each individual harmonic is sinusoidal.

3 Fundamental (60hz) & 5th Harmonic (300hz) 0 360

4 Sum of 60Hz & 300Hz (Fundamental & 5th harmonic) 0 360

5 Where Do Harmonics Originate? Harmonics primarily originate in electronic power converters. These can be found in: 1. Switch Mode Power Supplies 2. Electronic Ballasts 3. Variable Frequency Drives 4. Oven and Furnace Controls 5. Rectifier Circuits

6 Problems Created by Harmonic Currents 1. Overheated Neutrals 2. Overheated Transformers 3. Malfunctioning of Equipment due to excessive voltage distortion 4. Burned-out Motors 5. Tripped Circuit Breakers 6. Blown Fuses

7 TRIPLEN HARMONICS Triplen harmonics include the 3rd harmonic and all the odd multiples of the 3rd. Example: 3rd, 9th, 15th, 21st, 27th, 33rd, etc Note: Triplen harmonics tend to add up in the three phase neutral conductor.

8 TYPICAL 208Y/120 SYSTEM

9 EFFECTS on HARMONICS on TRANSFORMERS 1. Increased temperature rise 2. Increased neutral current flow 3. Increased core losses 4. Increased sound level 5. Decreased efficiency

10 K - FACTOR • A measure of a transformer’s ability to withstand the heating effects of non-sinusoidal harmonic currents created by much of today’s electronic equipment. • The stray losses of the transformer are multiplied by the K-Factor of the load resulting in increased heating of the unit.

11 TRANSFORMER CONDUCTOR LOSSES • Transformer conductor losses are composed of AC and DC losses. • AC losses = stray losses • DC losses = I^2 x R • Total conductor losses = AC + DC losses Note: Stray losses get multiplied by the K-factor of the load.

12 Example of TEMPERATURE RISE Typical 75 kVA TP1 75 kVA, 3-Ph, 480 - 208Y/120, 150 degree rise Total conductor losses at K-1 (linear load) = 2860 + 135 = 2995 If K=20 (non-linear load), new conductor losses are: 2860 + (20 x 135) = 5560 watts Rise @ K-1 = 150 degrees C Rise @ K-20 = 244 degrees C

13 Three Solutions to HARMONIC PROBLEMS 1. K - Rated Transformers (traditional) 2. Harmonic Mitigating Transformers (zig-zag) 3. I-Trap Neutral Current Reducer

14 K - Rated Transformers K - Rated or Non-Linear transformers do not eliminate harmonics! They are only designed to tolerate the heating effects of harmonics created by much of today's electronic equipment.

15 K-Rated (continued) K-rated transformers are traditional Delta-Wye transformers • They are designed with lower flux densities and no load losses as well as lower I²R losses resulting in a larger and heavier unit. • They do not eliminate or cancel harmonics

16 K-Factor Features Available in K-Factors of 4, 13, and 20 Aluminum or Copper windings. Available temperature rises of 150, 115, or 80 UL listed and CSA certified

17 K-Factor and TP1 • As of January 1, 2007 K-Rated transformers must comply to the efficiency standards (TP1) of the National Energy Bill • They are only required to comply with a connected load condition of K1 (no harmonics)

18 Acme Mitigating Transformer

19 Harmonic Mitigating Transformers How do they work? They consist of a Delta primary and a Zig-Zag secondary. The Zig-Zag secondary causes a phase shift in the triplen harmonics which results in a canceling effect. This prevents the triplen harmonic losses from being coupled back into the primary and results in cooler operation and increased energy efficiency.

20 What is a Zig-Zag winding? The secondary winding on each magnetic leg of the core is wound in two separate sections. These sections are Then transposed between different legs of the core to Create the Zig-Zag secondary. Each 120 v output of the transformer consists of two sections from different magnetic legs resulting in a magnetic phase shift

21 Diagram showing Delta primary and Zig-Zag secondary ( Zero degree angular displacement) X0

22 Harmonic Mitigating Catalog Numbers • CMT-53312-4S 30 KVA • CMT-53313-4S 45 KVA • CMT-53314-4S 75 KVA • CMT-53315-4S 112.5 KVA • CMT-53316-4S 150 KVA • CMT-53317-4S 225 KVA Optional “TVSS” available on 208Y/120 output

23 Harmonic Mitigating Benefits 1. Unlike K-Rated transformers, Mitigating transformers actually treat the triplen harmonics in the Zig-Zag secondary winding 2. Reduce supply voltage flat topping caused by non- linear loads 3. Improve overall power factor of supply system 4. Suitable for K-Factor loads 5. Improved energy efficiency (Meet TP1 at K-1 load)

24 Mitigating Transformer Features • Copper foil conductor to minimize “skin effect” of harmonic currents • Taps: 2 x 2.5% ANFC and BNFC • 220 Degree C insulation system with 150 Degree C rise • UL listed and CSA certified • Zero degree angular displacement between Primary and Secondary windings

25 Important Points to Remember • Harmonic mitigating transformers don’t treat harmonics or neutral current until they reach the transformer windings • Transformer has 200% Neutral Bar • Neutral conductor from transformer to Load Panel should be sized at 200%

26 ACME ADVANTAGES 1. Acme utilizes special winding techniques and “foil” conductors in both its K-Factor and Harmonic Mitigating transformers to minimize the heating effects of harmonic currents. (Skin effect) 2. The use of foil conductor increases the dielectric strength of the insulation because one layer is only one turn. Foil also eliminates the effects of axial forces which can result in failure of wire wound transformers.

27 Skin Effect Illustrated Round or rectangular magnet wire = = 60 Hz Higher Hz Foil conductor is very thin and much wider Minimizes skin effect at higher Hz No current flow in center of conductor - Skin effect Thinner but wider conductor Full current flow

28 Applications • Hospitals and Health Care Facilities • Commercial & Educational Facilities • Airport Facilities • Telecom Facilities • Broadcasting Facilities • Internet Service Providers • Data Centers

29 I-Trap Neutral Current Reducer Technical Description: • Low impedance - Zero sequence • Auto Zig-Zag transformer

30 I-Trap Applications 1. It is used to reduce excessive current flow in the neutral of a 3 phase 208Y/120 volt system. 2. It is available in ampere ratings of 100, 150, 300, and 450. It includes a front mounted amp meter for monitoring neutral current. 3. Target areas: Data processing centers, Hospitals, Radio and TV stations, Large computer labs, etc. (Any area having numerous electronic 120v loads powered from a 208Y/120 system)

31 How Does The I-Trap Work? • Third harmonic currents are “in-phase” (additive) in the three phase neutral. • The low impedance and auto Zig-Zag characteristics of the I-Trap target the third harmonic currents causing them to become “out of phase” in the three phase neutral, resulting in a canceling effect. Reductions of 50% to 90% are typical. • In many applications, the Acme I-Trap provides an easier and more affordable solution than replacing existing Neutral conductors.

32 I - TRAP PERFORMANCE Reduction in Phase Current: Before After Phase A 49.4 42.9 Phase B 39.2 40.1 Phase C 63.2 53.6 Average 50.6 45.5 Max phase amps reduced from 63.2 to 53.6 (18%) Phase unbalance reduced: Before - 62% ; After – 34%

33 Performance Data Phase A B C I-Trap Out In Out In Out In RMS 49.4 42.9 39.2 40.1 63.2 53.6 1H 39.0 40.0 31.0 38.0 51.0 50.0 3H 27.0 1.0 21.0 3.0 34.0 10.0 5H 13.0 15.0 11.0 13.0 15.0 16.0 7H 4.0 4.0 4.0 5.0 3.0 4.0 9H 1.0 --- 1.0 1.0 1.0 1.2 11H 1.0 --- 1.0 --- 1.0 --- Har. Dist. 78.2% 37.7% 77.6% 39.0% 73.2% 38.0% K – Factor 5.5 4.4 5.8 4.3 4.8 3.8

34 Reduction In Neutral Current I - Trap Out In RMS 84.8 8.1 1H 17.0 1.0 3H 83.0 8.0 5H 3.0 --- 7H 2.0 --- 9H 1.0 --- 11H 1.0 ---

35 Questions?

Add a comment

Related presentations

Presentación que realice en el Evento Nacional de Gobierno Abierto, realizado los ...

In this presentation we will describe our experience developing with a highly dyna...

Presentation to the LITA Forum 7th November 2014 Albuquerque, NM

Un recorrido por los cambios que nos generará el wearabletech en el futuro

Um paralelo entre as novidades & mercado em Wearable Computing e Tecnologias Assis...

Microsoft finally joins the smartwatch and fitness tracker game by introducing the...

Related pages

Transformers, Harmonic Currents and Phase Shifting

Transformers, Harmonic Currents and Phase Shifting Harmonic currents are omnipresent in electrical distribution systems and can cause a variety of problems.
Read more

HARMONICS

A harmonic canceling transformer is a relatively new power quality product for mitigating harmonic problems in electrical distribution systems.
Read more

Transformer Extra Losses Due To Harmonics | EEP

Harmonic voltages are generated in the impedance of the network by the harmonic load currents. In a transformer that is heavily loaded with harmonic
Read more

Harmonics in Transformers - YouTube

Andy Topinka of Technical Group Services discusses harmonics in transformers and how they can be detrimental to the power riser in your building.
Read more

Power Transformer Attenuates Harmonics | Content content ...

The mains of the world were constructed as a giant copper causeway to transport electricity from the generating station to our homes and factories. Today's ...
Read more

What is harmonics in a transformer - Answers - The Most ...

When discussing harmonics in relation to transformers, generally you're thinking of harmonics in the current waveform - if it's a 60Hz transformer,.
Read more

Third Harmonics in 3-Phase Transformer Operation

Third Harmonics in 3-Phase Transformer Operation. It was shown in Section 5-3 that the sinusoidal flux in iron cores requires a third-harmonic component in ...
Read more

Harmonic Mitigating Transformers - Schneider Electric

1 Data Bulletin 7400DB0301 July 2003 Nashville, TN, USA Harmonic Mitigating Transformers Application Guide Class 7400 ABOUT THIS DOCUMENT This document is ...
Read more

Effects of Harmonics on Power Systems - Electrical ...

If not properly designed or rated, electrical equipment will often malfunction when harmonics are present in an electrical system.Most people don't realize ...
Read more