1 TP1 Exemptions and Acme Products Acme’s single phase general purpose products in 15 and 25 kva are epoxy encapsulated which makes them exempt from TP1. Even though they are exempt they have efficiencies in the 96% to 98% range. Three phase general purpose products in 15 kva are also epoxy encapsulated and therefore are exempt from TP1. These units have efficiencies in the 96% to 97% range. This explains why the Catalog numbers for these products did not change. K-rated transformers are required to meet the TP1 standard when tested at a K- factor of 1. (no harmonics)

2 Single Phase TP1 Efficiencies Kva % 15 97.7 25 98.0 37.5 98.2 50 98.3 75 98.5 100 98.6 167 98.7 250 98.9

3 Three Phase TP1 Efficiencies Kva % 15 97.0 30 97.5 45 97.7 75 98.0 112.5 98.2 150 98.3 225 98.5 300 98.6 500 98.7 750 98.8 1000 98.9

4 TP1 Basics TP1 efficiency is calculated at 35% of rated kva load. Total losses in a transformer are the sum of the No Load (core) losses and the I²R (conductor) losses. A typical 75 kva TP1 unit would have 300 watts no load loss and 2900 watts I²R loss for total losses of 3200 watts.

5 TP1 Basics cont’d At 35% load the I²R losses would only be 355 watts (0.35² X 2900). The total losses would now be 300 + 355 = 655 watts. As you can see the no load losses have become almost 46% of the total losses. As a result of this it is necessary to address the no load losses in a transformer design to successfully meet the TP1 efficiency requirement.

6 TP1 Basics cont’d This is part of the reason why TP1 transformers are more expensive since the core is typically the most expensive component in the transformer. Another reason for higher cost is the required testing on 100% of units produced. Units must be tested under load conditions. (Additional labor and energy cost)

6 TP1 Basics cont’d This is part of the reason why TP1 transformers are more expensive since the core is typically the most expensive component in the transformer. Another reason for higher cost is the required testing on 100% of units produced. Units must be tested under load conditions. (Additional labor and energy cost)

Add a comment

Related presentations

Presentación que realice en el Evento Nacional de Gobierno Abierto, realizado los ...

In this presentation we will describe our experience developing with a highly dyna...

Presentation to the LITA Forum 7th November 2014 Albuquerque, NM

Un recorrido por los cambios que nos generará el wearabletech en el futuro

Um paralelo entre as novidades & mercado em Wearable Computing e Tecnologias Assis...

Microsoft finally joins the smartwatch and fitness tracker game by introducing the...

Related pages

Exemptions - Documents - docslide.us

Exemptions. Pub 4012 Tab C Pub 4491, Pg 35. Caution!. Exemptions and Filing Status encompass some of the most complex tax law issues Determining whether ...
Read more

Generator Classification and Exemptions Guide Final (1 ...

Download Generator Classification and Exemptions Guide Final (1) Transcript. X. Recommended. i8965 Exemptions (1) exempt Deductions and Exemptions Digests
Read more

NON-CONFORMITIES AND EXEMPTIONS AERONAUTICAL STUDIES ...

non-conformities and exemptions aeronautical studies. overview. introduction types of non-conformities what to do?
Read more

Personal and Additional Exemptions - Documents

×Close Share Personal and Additional Exemptions. Embed ...
Read more

1 Exemptions and special procedures CITES Secretariat ...

Slide 1 1 Exemptions and special procedures CITES Secretariat Slide 2 2 Overview The paragraphs of Article VII of the Convention list a number of cases for ...
Read more

Extraordinary and Medically Complex Exemptions for Testing.

(adsbygoogle = window.adsbygoogle || []).push({}); Slide 1 Extraordinary and Medically Complex Exemptions for Testing Slide 2 Exemptions from Assessment w ...
Read more

Assets and Exemptions Tutorial on entering asset and ...

Slide 1 Assets and Exemptions Tutorial on entering asset and exemption information in BkAssist® Slide 2 Scope of Tutorial This tutorial covers how you ...
Read more

Module 27 Nonbusiness Deductions and Exemptions

Module 27 Nonbusiness Deductions and Exemptions. Menu. Classification of deductible expenses Deductions for adjusted gross income Standard deduction and ...
Read more

NCC Direct Entry and Exemptions 2012-2013 (2) - Documents

NCC Entry requirements ... Home; Documents; NCC Direct Entry and Exemptions 2012-2013 (2)
Read more

Acme Electric Distributor | Wisconsin, Illinois, Indiana ...

Browse our extensive selection of Acme products. 1-800-318-4618. Items in Cart 0 View Cart » My Account » Sub Total $0.00
Read more