1. 65mm 540mm 65mm Page 1 TR Series Troffer LED Retrofit Kit Installation Instructions This installation guide is valid for the following Energy Solution’s retrofit kits: ARK22R24110D ARK22R24125D ARK22R30110D ARK22R30125D ARK24R40110D ARK24R40125D ARK24R50110D ARK24R50125D 2’ x 2’ 2’ x 4’ WIDTH/ 65mm 2’ x 4’ Length 2’ x 2’ Length 1183mm 572mm Dimension End rails (mounting bracket) Screw Hardware LED troffer

2. Page 2 TR Series Troffer LED Retrofit Kit Installation Instructions WARNING FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFI- CANT PROPERTY DAMAGE.For your protection, carefully read these warnings and instructions in their entirety before installing or maintaining this equip- ment. These instructions do not attempt to cover all installation and maintenance situations. WARNING: This retrofit must be installed by a quali- fied electrician in accordance with any NEC, CEC, state, and/or local code requirements. This retrofit kit is not for use with all fixture bodies. WARNING: Risk of fire or electric shock. Installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician. WARNING: Risk of fire or electric shock. Never connect to, disconnect from or service while circuit equipment is energized. WARNING: Risk of fire or electric shock. Luminaires wiring, power supply, or other electrical parts may be damaged when drilling for installation of retrofit assembly hardware. Inspect wiring and components for damage. WARNING: Risk of personal injury. This equipment may have sharp edges. Wear gloves to prevent cuts or abrasions when removing from carton, handling and maintaining this equipment. Do not install in a damaged fixture • This equipment must be installed in accordance with all federal, state and local laws, regulations and codes • Proper grounding is required to ensure personal safety •All service shall be performed by qualified service personnel •This equipment must be installed and modified in accordance with all federal, state and local laws, regulations and codes by a professional who is famil- iar with the construction and operation of this prod- uct and any hazards involved NOTICE: Do not install with total power input greater than power rating of original fixture WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. WARNING: Only those open holes indicated in the photographs and/or drawings may be made or al- tered as a result of kit installation. Do not leave any other open holes in an enclosure of wiring or electri- cal components Warnings

3. Page 3 TR Series Troffer LED Retrofit Kit Installation Instructions 1.Turn off power to fixture 2. Remove the lens, ballasts, socket bars and so on Remove the lamps. Remove the ballast cover. Remove the socket-bars, sockets, ballast and the wiring between the ballast and the sockets. 3. Install the side Rails Installation procedure Remove door/louver, ballast cover, socket bars, lampholders, ballast and wiring. Host Fixture Shell Figure2 - Mounting Rail fully installed Figure 1 Start with Mounting Rail at a slight angle, nested between the ceiling grid T-bar and the fixture housing

4. Page4 TR Series Troffer LED Retrofit Kit Installation Instructions 4. Suspend the LED Retrofit Insert from the Mounting Rails 5. Finalize installation of the LED Retrofit Insert. Figure 3 - Suspend LED Insert from Mounting Rails Figure4 - Securing the Latches Branch Wiring Entry Hinge Pin Pivot Hole Image of Completed Installation Position the LED Retrofit Insert in the host fixture opening so the driver is on the same end as the branch wiring entry point. With the Insert positioned vertically, insert the Hinge Pin on one end of the LED Retrofit Insert into the pivot hole in the Mounting Rail (Fig. 3). Align the Hinge Pin on the opposite corner with the slot in the Mounting Rail and slide the LED Retrofit Insert toward the corner of the host fixture until both Hinge Pins are located in the pivot holes. Complete the installation by rotating the LED Retrofit Insert so it is flush with the ceiling and secure it by rotating the latches (Fig. 4).